EN
UK Talk to us ↗
Partners / Solis

Solar optimisers for Solis inverters.

Archai is certified with Solis single-phase inverters and three-phase hybrids up to 10 kW. Keep the Solis inverter you already fit, add one iOPT 800W optimiser per panel and one GT gateway per string, and you get panel-level MPPT, per-panel monitoring in SolarSync and rapid shutdown to about 1 V at every panel.

Certified with Solis.

An optimiser changes how a string behaves. Certification means the combination has been tested, so you can quote it with confidence.

Solis logo
✓ Certified
● Certified compatible

Solis

Scope
Single-phase grid-tied and hybrid inverters, and three-phase hybrids up to 10 kW
Status
Solis manufacturer declaration (PDF)
Issued
September 2025
Warranty
Solis and Archai warranties stay valid when each product's requirements are followed
Not covered
Three-phase grid-tied, and three-phase hybrids above 10 kW. Ask us
Field proof
Stockport side-by-side test: 10% more with one panel shaded, 17% more under moving shade. Case study

Design rules on a Solis job.

Design the string to the Solis inverter exactly as you do now. Then add four checks.

  • One iOPT 800W per panel. Every panel in the string gets an optimiser.
  • One GT gateway per string, up to 30 optimisers. Two MPPT inputs with one string each means two GTs.
  • Every panel inside the optimiser's input limits (table).
  • A certified inverter. Solis single-phase, or a Solis three-phase hybrid up to 10 kW. For anything else, ask us first.
iOPT 800W input limits
Max input power800 W
Max input voltage70 V (check panel Voc)
Max input short-circuit current23 A (check panel Isc)
MPPT range12–60 V
Max system voltage1500 V
Worked example in the guide: 14 × 440 W panels on a Solis S5-EH1P5K-L hybrid, split 8 + 6 across a shaded south roof and a west roof. Two strings on two MPPT inputs, so the order is 14 × iOPT 800W and 2 × GT. See every check, with the Solis limits →

Commissioning notes.

Before the GT is live, each optimiser holds about 1 V. That gives you a pass or fail test at every panel.

01 / OPTIMISER

About 1 V

0.9–1.1 V at each OUT is normal. Above 1.1 V: replace. Below 0.9 V: check light and IN wiring.

02 / STRING

1 V × panels

A string of 8 reads about 8 V. Higher means a panel without an optimiser; lower means a loose or reversed connection.

03 / INVERTER

Solis waits

The string is below the Solis start-up voltage, so the inverter starts once the GT brings the optimisers out of the safe state.

04 / GT

10-minute self-test

Power the GT, run the self-test from its button, then map each optimiser in SolarSync.

Full test table, light codes and install order: Optimisers for Solis inverters: design rules and commissioning.

Solis questions.

Can you fit optimisers to a Solis inverter?

Yes, on Solis single-phase grid-tied and hybrid inverters and Solis three-phase hybrids up to 10 kW. Solis confirmed this in a manufacturer declaration issued in September 2025, which also says Solis and Archai warranties stay valid when each product's requirements are followed.

Do I need to change any settings on the Solis inverter?

Our install guide doesn't call for any Solis-specific settings. Set up the inverter as you normally would, then commission the GT gateway.

How many GT gateways do I need on a two-MPPT Solis inverter?

One GT per string. Two strings on two MPPT inputs need two GTs. Each GT handles up to 30 optimisers.

Why won't the Solis inverter start before the GT is commissioned?

Each optimiser holds about 1 V until the GT is live, so a 10-panel string shows about 10 V. That is below the Solis start-up voltage, so the inverter waits until the GT brings the optimisers out of the safe state.

Do optimisers work with Solis hybrid inverters and batteries?

Yes. The optimisers sit on the DC side between the panels and the inverter's PV input, so the battery side of a Solis hybrid is unaffected.

Next step

Spec it on your next job.

Datasheets, trade pricing and compatibility checks for installers, distributors and inverter manufacturers.